Operating instructions
Electronic pressure sensor
UK

80227599 / 00

05 / 2015

PN2xxx

Contents
1  Preliminary note ���������������������������������������������������������������������������������������������������4
1.1  Symbols used ������������������������������������������������������������������������������������������������4
2  Safety instructions �����������������������������������������������������������������������������������������������4
3  Functions and features ����������������������������������������������������������������������������������������4
3.1 Applications ���������������������������������������������������������������������������������������������������5
4 Function ���������������������������������������������������������������������������������������������������������������6
4.1  Communication, parameter setting, evaluation ���������������������������������������������6
4.2  Switching function ������������������������������������������������������������������������������������������7
4.3  Analogue function ������������������������������������������������������������������������������������������8
4.4 IO-Link �����������������������������������������������������������������������������������������������������������9
5 Installation ���������������������������������������������������������������������������������������������������������10
6  Electrical connection ������������������������������������������������������������������������������������������ 11
7  Operating and display elements ������������������������������������������������������������������������12
8 Menu ������������������������������������������������������������������������������������������������������������������13
8.1  Menu structure: main menu �������������������������������������������������������������������������13
8.2  Explanation of the menu ������������������������������������������������������������������������������14
8.2.1  Explanation of the menu level 1 ���������������������������������������������������������14
8.2.2  Explanation of the menu level 2 ���������������������������������������������������������14
9  Parameter setting ����������������������������������������������������������������������������������������������15
9.1  Parameter setting in general �����������������������������������������������������������������������15
9.2  Configure display (optional) �������������������������������������������������������������������������17
9.3  Set output signals ����������������������������������������������������������������������������������������18
9.3.1  Set output functions ����������������������������������������������������������������������������18
9.3.2  Define switching limits for the hysteresis function ������������������������������18
9.3.3  Define switching limits for the window function ����������������������������������18
9.3.4  Scaling of the analogue value ������������������������������������������������������������19
9.4  User settings (optional) ��������������������������������������������������������������������������������19
9.4.1  Set delay for the switching outputs �����������������������������������������������������19
9.4.2  Set output logic for the switching outputs �������������������������������������������19
9.4.3  Set damping for the switching signal ��������������������������������������������������19
9.4.4  Damping for analogue output �������������������������������������������������������������19
9.4.5  Zero-point calibration ��������������������������������������������������������������������������19
2

9.4.6  Read min/max values for the system pressure ����������������������������������20
9.4.7  Reset all parameters to factory setting �����������������������������������������������20
9.4.8  Set colour change of the display �������������������������������������������������������20
9.4.9  Graphical depiction of the colour change of the display ���������������������21
10 Operation ���������������������������������������������������������������������������������������������������������23
10.1  Read set parameters ���������������������������������������������������������������������������������23
10.2  Self-diagnosis / error indications ���������������������������������������������������������������24
11  Technical data and scale drawing ��������������������������������������������������������������������25
11.1  Setting ranges ��������������������������������������������������������������������������������������������25 UK
11.2  Further technical data ��������������������������������������������������������������������������������27
12  Factory setting �������������������������������������������������������������������������������������������������28

3

1  Preliminary note
1.1  Symbols used

>
[…]


Instructions
Reaction, result
Designation of keys, buttons or indications
Cross-reference
Important note
Non-compliance may result in malfunction or interference
Information
Supplementary note

2  Safety instructions
• Please read this document prior to set-up of the unit. Ensure that the product is
suitable for your application without any restrictions.
• If the operating instructions or the technical data are not adhered to, personal
injury and/or damage to property can occur.
• Check the compatibility of the product materials with the media to be measured
in all applications.
• Correct condition of the device for the operating time can only be guaranteed if
the device is only used for media to which the wetted materials are sufficiently
resistant → 3.1 Applications.
• If the devices are used in gas applications with pressures > 25 bar the notes in
chapter 3.1 for devices with the marking **), must be absolutely observed!
The responsibility whether the measurement device is suitable for the
respective application lies with the operator. The manufacturer assumes
no liability for consequences of misuse by the operator. Improper
installation and use of the devices result in a loss of the warranty claims.

3  Functions and features
The device monitors the system pressure of machines and installations.

4

3.1  Applications
Type of pressure: Relative pressure

Pressure resistance
Bursting
Measuring range
(max. permissible
pressure
pressure) *)
bar
psi
bar
psi
bar
psi
Pressure sensors with G¼ internal thread
PN2160
0...600
0…8700
800
11580
2500 36250
PN2070
0...400
0…5800
800
11580
1700 24650
PN2071
0...250
0…3625
500
7250
1200 17400
UK
PN2092**
0...100
0…1450
300
4350
650
9400
PN2093**
-1...25
-14.5…362.5
150
2175
350
5075
PN2094**
-1...10
-14.6…145
75
1087
150
2175
PN2096
-0.125...2.5 -1.8…36.25
20
290
50
725
mbar
psi
mbar
psi
mbar
psi
PN2099
-1000...1000 -14.5...14.5
20000
290
50000
725
PN2097
-50...1000 -0.72…14.5
10000
145
30000
450
PN2169
-500...500
-7.26...7.26
10000
145
30000
450
PN2098
-12.5...250
-10000
-30000
-Pressure sensors with G¼ external thread
PN2560
0...600
0…8700
800
11580
2500 36250
PN2570
0...400
0…5800
800
11580
1700 24650
PN2571
0...250
0…3625
500
7250
1200 17400
PN2592**
0...100
0…1450
300
4350
650
9400
PN2593**
-1...25
-14.5…362.5
150
2175
350
5075
PN2594**
-1...10
-14.6…145
75
1087
150
2175
PN2596
-1.25...2.5 -1.8…36.25
20
290
50
725
mbar
psi
mbar
psi
mbar
psi
PN2599
-1000...1000 -14.5...14.5
20000
290
50000
725
PN2597
-50...1000 -0.72…14.5
10000
145
30000
450
PN2569
-500...500
-7.26...7.26
10000
145
30000
450
PN2598
-12.5...250
-10000
-30000
-*) With static overload pressure or max. 100 million pressure cycles.

**) Use
devices with a measuring range ≥ 250 bar for gas applications > 25 bar!
For a measuring range of 0...100 bar the PN7 series (PN7072 or PN7572) with 2 switch
points can be used for gas applications.
MPa = (measured value in bar) ÷ 10
kPa = (measured value in bar) x 100
Order
number

5

Avoid static and dynamic overpressure exceeding the specified overload
pressure by taking appropriate measures.
The indicated bursting pressure must not be exceeded.
Even if the bursting pressure is exceeded only for a short time, the unit
may be destroyed. ATTENTION: Risk of injury!
The units are vacuum resistant. With a nominal pressure range ≤
300 mbar observe the specifications in the data sheet!
Pressure Equipment Directive (PED):
The units comply with the Pressure Equipment Directive and are designed
and manufactured for group 2 fluids in accordance with the sound
engineering practice.
Use of group 1 fluids on request!

4  Function
• The unit displays the current system pressure.
• It generates output signals according to the operating mode and the parameter
setting.
• It moreover provides the process data via IO-Link.
• The unit is laid out for fully bidirectional communication. So, the following
options are possible:
-- Remote display: reading and display of the current system pressure.
-- Remote parameter setting: reading and changing the current parameter
setting.
-- IO-Link parameter setting → 4.4.
4.1  Communication, parameter setting, evaluation
OUT1 (pin 4)
OUT2 (pin 2)

6

• Switching signal for system pressure limit value
• Communication via IO-Link
• Switching signal for system pressure limit value
• Analogue signal 4...20 mA / 0...10 V

4.2  Switching function
OUTx changes its switching status if it is above or below the set switching limits
(SPx, rPx). The following switching functions can be selected:
• Hysteresis function / normally open: [ou1/ou2] = [Hno] (→ fig. 1).
• Hysteresis function / normally closed: [ou1/ou2] = [Hnc] (→ fig. 1).
First the set point (SPx) is set, then the reset point (rPx).
The hysteresis defined remains even if SPx is changed again.
• Window function / normally open: [ou1/ou2] = [Fno] (→ fig. 2).
• Window function / normally closed: [ou1/ou2] = [Fnc] (→ fig. 2).
The width of the window can be set by means of the difference between FHx
and FLx. FHx = upper value, FLx = lower value.
1








UK

2
FH
FL










P = system pressure; HY = hysteresis; FE = window

When set to the window function the set and reset points have a fixed
hysteresis of 0.25 % of the final value of the measuring span.

7

4.3  Analogue function
OUT2 is an analogue output:
• [ou2] defines whether the set measuring range is provided as
4...20 mA ([ou2]= [I]) or as 0...10 V ([ou2] = [U]).
• Analogue start point [ASP2] determines at which measured value the output
signal is 4 mA or 0 V.
• Analogue end point [AEP2] determines at which measured value the output
signal is 20 mA or 10 V.
Minimum distance between [ASP2] and [AEP2] = 20 % of the measuring span.
Voltage output 0...10 V:
Factory setting

Measuring range scaled























P=
System pressure
VMR = Final value of the measuring range
ASP = Analogue start point [ASP2]
AEP= Analogue end point [AEP2]
In the measuring range of the respective unit the output signal is between 0 and 10 V.
It is also indicated:
• System pressure above [AEP2]: 10...10.3 V
• Fault indication according to Namur: 11 V

8

Current output 4...20 mA
Factory setting

Measuring range scaled












UK
















P=
System pressure
VMR = Final value of the measuring range
ASP = Analogue start point [ASP2]
AEP= Analogue end point [AEP2]
In the measuring range, the output signal is between 4 and 20 mA.
It is also indicated:
• System pressure above [AEP2]: 20...20.5 mA
• System pressure below [ASP2]: 4...3.8 mA
• Fault indication according to Namur: 21.5 mA.

4.4  IO-Link
General information
This unit has an IO-Link communication interface which requires an IO-Linkcapable module (IO-Link master) for operation.
The IO-Link interface enables direct access to the process and diagnostic data
and provides the possibility to set the parameters of the unit during operation.
In addition communication is possible via a point-to-point connection with a USB
adapter cable.
Further information about IO-Link at www.ifm.com → "more product information"
→ "Specials" → "IO-Link".

9

Device-specific information
You can find the IODDs necessary for the configuration of the IO-Link unit and
detailed information about process data structure, diagnostic information and
parameter addresses at www.ifm.com → "more product information" → "Specials"
→ "IO-Link".
Parameter setting tools
You will find all necessary information about the required IO-Link hardware and
software at www.ifm.com → "more product information" → "Specials" → "IO-Link".

5  Installation

Before installing and removing the unit: make sure that no pressure is
applied to the system.
► Insert the unit in a G¼ process connection.
► Tighten firmly. Recommended tightening torque:
Pressure range in bar Tightening torque in Nm
-1...400
25...35
600
30...50
Depends on lubrication, seal and pressure load!

The sensor housing can be rotated by 345° with regard to the process connection.
Do not rotate past the end stop!

10

6  Electrical connection

The unit must be connected by a qualified electrician.
The national and international regulations for the installation of electrical
equipment must be adhered to.
Voltage supply according to EN 50178, SELV, PELV.

►► Disconnect power.
►► Connect the unit as follows:
Core colours
BK
black
BN
brown
BU
blue
WH
white

2
3

2 x positive switching
1 BN
2 WH

1
4

3 BU

BN

2

WH

4

BK

3

BU

UK

L+
OUT2
OUT1
L

OUT1: switching output or IO-Link
OUT2: switching outputs or analogue output
Colours to DIN EN 60947-5-2
Example circuit
2 x negative switching
1 BN

L+

2 WH

4 BK
2: OUT2
4: OUT1

1

L+

4 BK
L

2: OUT2
4: OUT1

3 BU

L

1 x positive switching / 1 x analogue

1 x negative switching / 1 x analogue

1 BN

1 BN

2 WH

L+

2 WH
4 BK

4 BK
2: OUT2
4: OUT1

3 BU

L+

L

2: OUT2
4: OUT1

3 BU

L

11

7  Operating and display elements
1

2

9

3

4

5

10

6

7

8

11

12

1 to 8: indicator LEDs
LED 1
Switching status OUT1 (lights when output 1 is switched).
LED 8
Switching status OUT2 (lights when output 2 is switched).
LEDs
System pressure in the indicated unit of measurement
2-7
(pin connection is device-specific).
9: Enter button [●]
-- Selection of the parameters and acknowledgement of the parameter values.
10 to 11: Arrow keys up [▲] and down [▼]
-- Setting of the parameter values (scrolling by holding pressed; incremental by pressing
once).
12: Alphanumeric display, 4 digits
-- Display of the current system pressure.
-- Indication of the parameters and parameter values.

12

8  Menu

8.1  Menu structure: main menu
2

RUN
1

Menu items highlighted in grey e.g. [ FH1
] are only active when assigned parameters
have been selected.

13

8.2  Explanation of the menu
8.2.1  Explanation of the menu level 1

SPx / rPx Upper / lower limit value for system pressure at which OUTx switches with
hysteresis setting. Prerequisite: OUTx setting is [Hno] or [Hnc].
FHx / FLx Upper / lower limit value for system pressure at which OUTx switches with
window setting. Prerequisite: OUTx setting is [Fno] or [Fnc].
ASP2
Analogue start point for system pressure: measured value at which 4 mA / 0 V
are provided. Prerequisite: OUT2 setting is [I] or [U].
AEP2
Analogue end point for system pressure: measured value at which
20 mA / 10 V are provided. Prerequisite: OUT2 setting is [I] or [U].
EF
Extended functions / opening of menu level 2.

8.2.2  Explanation of the menu level 2
rES
ou1

Restore factory setting.
Output function for OUT1:
• Switching signal for the pressure limit values: hysteresis function [H ..] or
window function [F ..], either normally open [. no] or normally closed [. nc].
ou2
Output function for OUT2:
• Switching signal for the pressure limit values: hysteresis function [H ..] or
window function [F ..], either normally open [. no] or normally closed [. nc].
• Analogue signal for the current system pressure: 4...20 mA [I] or 0...10 V [U].
dS1 / dS2 Switching delay for OUT1 / OUT2.
dr1 / dr2

Switch-off delay for OUT1 / OUT2.
Standard unit of measurement for system pressure (display):
uni
[bAr] / [mbar] / [MPA] / [kPA] / [PSI] / [inHG] / [iH2O] / [mmWS] .
P-n
Output logic: pnp / npn.
Lo
Minimum value memory for system pressure.
Hi
Maximum value memory for system pressure.
dAP
Damping of the switch point.
Damping of the analogue output.
dAA
Prerequisite: OUT2 setting is [I] or [U].
coF
Zero-point calibration.
Assignment of the display colours "red" and "green" within the measuring
coLr
range.
Upper / lower value for colour change. Parameter only active after selection of
cFH / cFL
a freely definable colour window in the coLr parameter: [r-cF] or [G-cF].
diS
Update rate and orientation of the display.

14

9  Parameter setting
During parameter setting the unit remains in the operating mode. It continues
to monitor with the existing parameters until the parameter setting has been
completed.
9.1  Parameter setting in general
3 steps must be taken for each parameter setting:
1

Select parameter
► Press [●] to get to the menu.
UK
► Press [▲] or [▼] until the requested
parameter is displayed.

2

3

Set parameter value
► Press [●] to edit the selected
parameter.
► Press [▲] or [▼] for min. 1 s.
>> After 1 s: setting value is changed:
incrementally by pressing the button
once or continuously by keeping the
button pressed.
Numerical values are incremented continuously with [▲] or decremented with [▼].
Acknowledge parameter value
► Briefly press [●].
>> The parameter is displayed again.
The new setting value is saved.

Set other parameters
► Press [▲] or [▼] until the requested parameter is displayed.
Finish parameter setting
► Press [▲] or [▼] several times until the current measured value is displayed or wait for
30 s.
>> The unit returns to the process value display.

15

If [C.Loc] is displayed when an attempt is made to modify a parameter
value, a parameter setting process is active via the IO-Link communication
(temporary locking).
If [S.Loc] is displayed, the sensor is permanently locked via software. This
locking can only be removed with a parameter setting software.
• Change from menu level 1 to menu level 2:
► Press [●] to get to the menu.

► Press [▲] [▼]until [EF] is displayed.

► Press [●].
>> The first parameter of the submenu is
displayed (here: [rES]).

• Locking / unlocking
The unit can be locked electronically to prevent unintentional settings.
► Make sure that the unit is in the
normal operating mode.
► Press [▲] + [▼] simultaneously for
10 s.
>> [Loc] is displayed.

10 s
During operation: [Loc] is briefly displayed if you try to change parameter values.

16

For unlocking:
► Make sure that the unit is in the
normal operating mode.
► Press [▲] + [▼] simultaneously for
10 s.
>> [uLoc] is displayed.

10 s

On delivery: not locked.

• Timeout:
If no button is pressed for 30 s during parameter setting, the unit returns to the
operating mode with unchanged values.

UK

• Exit a parameter without adopting the settings
To exit a parameter without adopting the
settings:
► Press [▲] + [▼] simultaneously.
>> Return to the menu level.

• Leaving the menu level
To leave the menu level:
► Press [▲] + [▼] simultaneously.
>> Menu level 2 changes to level 1
or
level 1 changes to display.

9.2  Configure display (optional)
► Select [Uni] and set the unit of measurement:
-- [bAr], [mbAr],
-- [MPA], [kPA],
-- [PSI],
-- [inHG],
-- [iH2O],
-- [mmWS]

The selectable units of measurement depend on the
respective unit.
17

►► Select [diS] and set the update rate and orientation of the display:
-- [d1]: update of the measured values every 50 ms.
-- [d2]: update of the measured values every 200 ms.
-- [d3]: update of the measured values every 600 ms.
-- [rd1], [rd2], [rd3]: display as for d1, d2, d3; rotated by 180°.
-- [OFF ] = The display is switched off in the operating mode. When
one of the buttons is pressed, the current measured value is
displayed for 30 s. The LEDs remain active even if the display
is deactivated.
Even with unsteady pressure characteristics [d1] provides optimum
readability; the corresponding algorithms are stored.

9.3  Set output signals
9.3.1  Set output functions
►► Select [ou1] and set the switching function:
-- [Hno] = hysteresis function/NO,
-- [Hnc] = hysteresis function/NC,
-- [Fno] = window function/NO,
-- [Fnc] = window function/NC.
►► Select [OU2 ] and set the analogue function:
-- [Hno] = hysteresis function/NO,
-- [Hnc] = hysteresis function/NC,
-- [Fno] = window function/NO,
-- [Fnc] = window function/NC.
-- [I] = current signal 4...20 mA,
-- [U] = voltage signal 0...10 V.

9.3.2  Define switching limits for the hysteresis function
►► [ou1] / [ou2] must be set as [Hno] or [Hnc].
►► Select [SPx] and set the value at which the output is set.
►► Select [rPx] and set the value at which the output resets.
rPx is always smaller than SPx. The unit only accepts values which are lower
than the value for SPx.

9.3.3  Define switching limits for the window function
►► [ou1] /[ou2] must be set as [Fno] or [Fnc].
►► Select [FHx] and set the upper limit value.

18

► Select [FLx] and set the lower limit value.
FLx is always lower than FHx. The unit only accepts values which are lower
than the value for FHx.

9.3.4  Scaling of the analogue value
► Select [ASP2] and set the value at which 4 mA / 0 V is provided.
► Select [AEP2] and set the value at which 20 mA / 10 V is provided.
Minimum distance between ASP2 and AEP2 = 20 % of the measuring
span (scaling factor 5).
UK

9.4  User settings (optional)
9.4.1  Set delay for the switching outputs

[dS1] / [dS2] = switching delay for OUT1 / OUT2.
[dr1] / [dr2] = reset delay for OUT1 / OUT2.
► Select [dS1], [dS2], [dr1] or [dr2] and set a value between 0 and 50 s (at
0 the delay time is not active).
For this unit the parameters [dSx] and [drx] for the set and reset
points are designed strictly to the VDMA guideline.

9.4.2  Set output logic for the switching outputs
► Select [P-n] and set [PnP] or [nPn].

9.4.3  Set damping for the switching signal

► Select [dAP] and set the damping constant in seconds
(value T: 63 %); setting range 0.000...4.000 s.
Damping affects [dAP] the switch point / process data flow (IO-Link
communication) and the display.

9.4.4  Damping for analogue output

► Select [dAA] and set the damping constant (rise time 10...90 %) in
seconds; setting range 0.000...4.000 s.
Damping [dAA] only affects the analogue output / analogue signal
path.

9.4.5  Zero-point calibration

► Select [coF] and set a value between -5 % and 5 % of the final value
of the measuring range (if PN2x69 and PN2x99 ±5 % of the measuring
span). The internal measured value "0" is shifted by this value.

19

9.4.6  Read min/max values for the system pressure
►► Select [HI] or [Lo] and briefly press [●].
[HI] = maximum value, [Lo] = minimum value.
Delete memory:
►► Select [HI] or [Lo].
►► Press and hold [▲] or [▼] until [----] is displayed.
►► Briefly press [●].

9.4.7  Reset all parameters to factory setting
►► Select [rES].
►► Press [●].
►► Press and hold [▲] or [▼] until [----] is displayed.
►► Briefly press [●].
We recommend noting down your own settings before carrying out a reset
(→ 12 Factory setting).

9.4.8  Set colour change of the display

►► Select [coLr] and set the function:
-- [rEd] = display colour red (independent of the measured value).
-- [GrEn] = display colour green (independent of the measured value).
-- [r1ou] = display colour red when OUT1 switches.
-- [G1ou] = display colour green when OUT1 switches.
-- [r2ou] = display colour red when OUT2 switches ([ou2] = [Hxx] /
[Fxx]).
-- [G2ou] = display colour green when OUT2 switches ([ou2] = [Hxx] /
[Fxx]).
-- [r-12] = display colour red when the measured value is between the
limit values of OUT1 and OUT2 ([ou2] = [Hxx] / [Fxx]).
-- [G-12] = display colour green when the measured value is between
the limit values of OUT1 and OUT2 ([ou2] = [Hxx] / [Fxx]).
-- [r-cF] = display colour red when the measured value is between the
freely definable limit values [cFH]*) and [cFL]*).
-- [G-cF] = display colour green when the measured value is between
the freely definable limit values [cFH]*) und [cFL]*)

*) The
parameters [cFL] and [cFH ] can only be selected in the menu tree
when [r-cF] or [G-cF] were activated.
►► Select [cFH] and set the upper limit value.
(only possible when [r-cF] or [G-cF] were activated).
>> The setting range corresponds to the measuring range and its minimum
limit is [cFL].

20

► Select [cFL] and set the lower limit value
(only possible when [r-cF] or [G-cF] were activated).
>> The setting range corresponds to the measuring range and its maximum
limit is [cFH].

9.4.9  Graphical depiction of the colour change of the display
Display colour change for the parameters
[r1ou] / [r2ou], mode hysteresis function

Display colour change for the parameters
[G1ou] / [G2ou], mode hysteresis function
UK

OUT1/
OUT2

OUT1/
OUT2

1

2

1

2

Measured value > switch point OUT1/OUT2; Measured value > switch point OUT1/OUT2;
Display = red
Display = green
Display colour change for the parameters
[r1ou] / [r2ou], mode window function

Display colour change for the parameters
[G1ou] / [G2ou], mode window function

FH1/
FH2
FL1/
FL2

FL1/
FL2

1

2

easured value between FL1/FL2 and
M
FH1/FH2; Display = red

1
2

FH1/
FH2

1

2

Measured value between FL1/FL2 and
FH1/FH2; Display = green

Colour change display green
Colour change display red
Initial value of the measuring range
Final value of the measuring range

21

Representation [r-12] / [G-12] only possible when [ou2] = switching output.
Display colour change for the parameters
[r-12], mode hysteresis function

Display colour change for the parameters
[G-12], mode hysteresis function
OUT2

OUT2

OUT1

OUT1

1

1

2

2

Measured value between OUT1 and OUT2; Measured value between OUT1 and OUT2;
Display = red
Display = green
Display colour change for the parameters
[r-12], mode window function

Display colour change for the parameters
[G-12], mode window function

FL2

FH1

FL2

FH1

FL1

FH2
1

2

easured value outside FL1...FH1 and
M
FL2...FH2; Display = red

FH2

FL1
1

Measured value outside FL1...FH1 and
FL2...FH2; Display = green

Colour change display green
Colour change display red
1
Initial value of the measuring range
2
Final value of the measuring range
FL1 / FL2 Lower limit value window function outputs OUT1 / OUT2
FH1 / FH2 Upper limit value window function outputs OUT1 / OUT2

22

2

Display colour change with parameter [r-cF] Display colour change with parameter
independent of OUT1.
[G-cF] independent of OUT1.

cFH

cFL
1

2

Measured value between cFL and cFH;
Display = red

1
2
cFL
cFH

UK

cFH

cFL
1

2

Measured value between cFL and cFH;
Display = green

Colour change display green
Colour change display red
Initial value of the measuring range
Final value of the measuring range
Lower limit value (independent of the output function)
Upper limit value (independent of the output function)

10  Operation
After power on, the unit is in the Run mode (= normal operating mode). It carries
out its measurement and evaluation functions and provides output signals
according to the set parameters.
Operation indication → 7 Operating and display elements.
10.1  Read set parameters
► Press [●].
► Press [▲] or [▼] until the requested parameter is displayed.
► Briefly press [●].
>> The unit displays the corresponding parameter value for approx. 30 s; then it
changes to the process value display.
23

none

Type of fault *)

Status LED
OUT2

Status LED
OUT1

Display

10.2  Self-diagnosis / error indications
The unit has many self-diagnostic options.
• It monitors itself automatically during operation.
• Warnings and faults are displayed (even if the display is deactivated), in
addition they are available via the parameter setting software.

F

SC
flashes flashes
flashes

F

SC1 flashes
flashes

F

SC2
flashes

flashes

F

Fault / warning
Supply voltage too
low.
Excessive current
at switching outputs
OUT1 and OUT2 **).
Excessive current
at switching output
OUT1 **).
Excessive current
at switching output
OUT2 **).

Loc

W Parametrierung über
Tasten gesperrt.

C.Loc

W Parameter
setting locked
via pushbuttons,
parameter setting
is active via IO-Link
communication
→ 9.1.
W Setting buttons
locked via parameter
software. Parameter
change is rejected
→ 9.1.

S.Loc

24

Corrective measures
► Check / correct the supply
voltage.
► Check switching outputs for
short-circuit or excessive
current; remove the fault.
► Check switching output
OUT1 for short-circuit or
excessive current; remove
the fault.
► Check switching output
OUT2 for short-circuit or
excessive current; remove
the fault.
► Unlock buttons → 9.1
Parameter setting in general
→"Locking / unlocking“.
► Wait until parameter setting
via IO-Link is finished.

► Unlocking only possible via
IO-Link interface / parameter
setting software.

Type of fault *)

Status LED
OUT2

Status LED
OUT1

Display

Fault / warning

Corrective measures

► Check / reduce system
W Process value too
pressure / select unit with
high
corresponding measuring
(measuring range
range.
exceeded).
W Process value too low ► Check / increase system
(value below
pressure / select unit with
measuring range).
corresponding measuring
range.
► Contact the manufacturer.
F Internal fault /
malfunction.

OL

UL

Err
flashes

*) F = fault

UK

W = warning
**) The output remains deactivated as long as the excessive current / short circuit
continues.

11  Technical data and scale drawing
11.1  Setting ranges
SP
rP
ASP2
AEP2
min max min max min max min max
PN-2093 -0�85
BAR

25

-0�95 24�9

-1

20

4

25

cFH
cFL
ΔP
min max min max
-0�9

25

-1

24�9 0�05

25

12  Factory setting
SP1
rP1
ou1
ou2
SP2
rP2
ASP2
AEP2
coF
dSx
drx
P-n
dAP
dAA
diS
uni
coLr
cFH
cFL

Factory setting
25% MEW***
23% MEW***
Hno
I
75% MEW***
73% MEW***
0
(PN2x99: -996 mbar)
(PN2x69: -500 mbar)
100% MEW *
0
0.0
0.0
PnP
0.06
0.1
d2
bAr / mbAr
rEd
VMR*
MAW**

User setting

* = Final value of the measuring range (MEW)
** = Initial value of the measuring range (MAW)
*** = The indicated percentage of the final value of the measuring range (VMR) of the
respective sensor (for PN2x69 and PN2x99 the percentage of the measuring span)
is set.

More information at www.ifm.com